Performance Specifications
Item | CP1E-E[][]SD[]-[] CP1E-[][]D[]-[] |
CP1E-N[][]S[]D[]-[] CP1E-N[][]D[]-[] CP1E-NA[][]D[]-[] |
||
---|---|---|---|---|
Program capacity | 2 K steps (8 Kbytes) including the symbol table, comments, and program indices of the CX-Programmer |
8 K steps (32 Kbytes) including the symbol table, comments, and program indices of the CX-Programmer |
||
Control method | Stored program method | |||
I/O control method | Cyclic scan with immediate refreshing | |||
Program language | Ladder diagram | |||
Instructions | Approximately 200 | |||
Proc- essing speed |
Overhead processing time | 0.4 ms | ||
Instruction execution times | Basic instructions (LD): 1.19 µs min. Special instructions (MOV): 7.9 µs min. |
|||
Number of CP1W-series Expansion Units connected |
CP1E-E10D[]-[]/[]14(S)D[]-[]/[]20(S)D[]-[]: None CP1E-[]30(S[])D[]-[]/[]40(S[])D[]-[]/[]60(S[])D[]-[]/NA20(S[])D[]-[]: 3 units |
|||
Maximum number of I/O points | CP1E-E10D[]-[]: 10 CP1E-[]14(S)D[]-[]: 14 CP1E-[]20(S)D[]-[]: 20 CP1E-[]30(S[])D[]-[]: 150 (30 built in, 40 × 3 expansion) CP1E-[]40(S[])D[]-[]: 160 (40 built in, 40 × 3 expansion) CP1E-[]60(S[])D[]-[]: 180 (60 built in, 40 × 3 expansion) CP1E-NA20D[]-[]: 140 (20 built in, 40 × 3 expansion) |
|||
Built-in I/O | CP1E-E10D[]-[]: 10 (6 inputs, 4 outputs) CP1E-[]14(S)D[]-[]: 14 (8 inputs, 6 outputs) CP1E-[]20(S)D[]-[]: 20 (12 inputs, 8 outputs) CP1E-[]30(S[])D[]-[]: 30 (18 inputs, 12 outputs) CP1E-[]40(S[])D[]-[]: 40 (24 inputs, 16 outputs) CP1E-[]60(S[])D[]-[]: 60 (36 inputs, 24 outputs) CP1E-NA20D[]-[]: 20 (12 inputs, 8 outputs) |
|||
Built-in input func- tions |
High- speed counters |
High-speed counter mode/ maximum frequency |
Incremental Pulse Inputs 10 kHz: 6 counters 5 counters (only for 10 I/O points) Up/Down Inputs 10 kHz: 2 counters Pulse + Direction Inputs 10 kHz: 2 counters Differential Phase Inputs (4x) 5 kHz: 2 counters |
Incremental Pulse Inputs 100 kHz: 2 counters, 10 kHz: 4 counters Up/Down Inputs 100 kHz: 1 counters, 10 kHz: 1 counters Pulse + Direction Inputs 100 kHz: 2 counters Differential Phase Inputs (4x) 50 kHz: 1 counter, 5 kHz: 1 counter |
Counting mode | Linear mode Ring mode |
|||
Count value | 32 bits | |||
Counter reset modes |
Phase Z and software reset (excluding increment pulse input) Software reset |
|||
Control method | Target Matching Range Comparison |
|||
Input interrupts | 6 inputs (4 inputs only for 10 I/O points) Interrupt input pulse width: 50 µs min. |
|||
Quick-response Inputs | 6 inputs (4 inputs only for 10 I/O points) Input pulse width: 50 µs min. |
|||
Normal input |
Input constants | Delays can be set in the PLC Setup (0 to 32 ms, default: 8 ms). Set values: 0, 1, 2, 4, 8, 16, or 32 ms |
||
Built-in output func- tions |
Pulse outputs (Models with transistor outputs only) |
Pulse output method and output frequency |
Pulse output function not included |
Pulse + Direction Mode 1 Hz to 100 kHz: 2 outputs |
Output mode | Continuous mode (for speed control) Independent mode (for position control) |
|||
Number of output pulses |
elative coordinates: 0000 0000 to 7FFF FFFF hex (0 to 2147483647) Absolute coordinates: 8000 0000 to 7FFF FFFF hex (-2147483647 to 2147483647) |
|||
Acceleration/ deceleration curves |
Trapezoidal acceleration and deceleration (Cannot perform S-curve acceleration and deceleration.) |
|||
Changing SVs during instruction execution |
Only target position can be changed. | |||
Origin searches | Included | |||
Pulse outputs (Models with transistor outputs only) |
Frequency | PWM output function not included |
2.0 to 6,553.5 Hz (in increments of 0.1 Hz) with 1 output or 2 Hz to 32,000 Hz (in increments of 1 Hz) with 1 output |
|
Duty factor | 0.0% to 100.0% (in increments of 0.1%) Accuracy: +1%/-0% at 2 Hz to 10,000 Hz and +5%/-0% at 10,000 Hz to 32,000 kHz |
|||
Output mode | Continuous Mode | |||
Built-in analog | Analog input | Analog function not included | Setting range: 0 to 6,000 (2 channels only for NA-type) |
|
Analog output | Setting range: 0 to 6,000 (1 channels only for NA-type) |
|||
Analog adjusters | E/N/NA[][]-type: 2 adjusters (Setting range: 0 to 255) E/N[][]S(1)-type: None |
|||
Com- muni- cations |
B-type Peripheral USB Port | Conforming to USB 2.0 B type connector | ||
Transmission distance |
5 m max. | |||
Built-in RS-232C port | No built-in RS-232C port | Interface: Conforms to EIA RS-232C. | ||
Communications method |
Half duplex | |||
synchronization | Start-stop | |||
Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps |
|||
Transmission distance |
15 m max. | |||
Supported protocol |
• Host Link • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU Easy Master |
|||
Built-in RS-485 port | No built-in RS-485 port | N30/40/60S1-type only Interface: Conforms to EIA RS-485. 2-wire sensors No isolation |
||
Communications method |
Half duplex | |||
synchronization | Start-stop | |||
Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps |
|||
Transmission distance |
50 m max. | |||
Supported protocol |
• Host Link • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU Easy Master |
|||
Serial Option port | Option Board cannot be mounted. |
N30/40/60 and NA20-type only 1 port |
||
Mountable Option Boards |
One RS-232C port: CP1W-CIF01 One RS-422A/485 port (not isolated): CP1W-CIF11 One RS-422A/485 port (isolated): CP1W- CIF12 One Ethernet port: CP1W-CIF41 |
|||
Communications method |
Depends on Option Board. | |||
synchronization | Depends on Option Board. | |||
Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps |
|||
Compatible protocols |
• Host Link • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU Easy Master |
|||
Number of tasks | 17 • One cyclic execution task • One scheduled interrupt task (always interrupt task 1) • Six input interrupt tasks (interrupt tasks 2 to 7) • Sixteen high-speed counter interrupt tasks (interrupt tasks 1 to 16) |
|||
Maximum subroutine number | 128 | |||
Maximum jump number | 128 | |||
Scheduled interrupt tasks | 1 interrupt task | |||
Clock | Clock function not included. The time of error occurrence displays 01-01-01 01:01:01 Sunday |
Included. Accuracy (monthly deviation): -4.5 min to -0.5 min at ambient temperature of 55°C, -2.0 min to +2.0 min at ambient temperature of 25°C, -2.5 min to +1.5 min at ambient temperature of 0°C |
||
Memory backup |
Built-in EEPROM | Ladder programs and parameters are automatically saved to built-in EEPROM A section of the Data Memory Area can be saved to the built-in EEPROM. |
||
Battery backup With CP1W-BAT01 Battery (Sold separately) |
Battery cannot be mounted. | CP1W-BAT01 can be used. Maximum battery service life: 5 years Backup Time Guaranteed value (ambient temperature: 55°C): 13,000 hours (approx. 1.5 years) Effective value (ambient temperature: 25°C): 43,000 hours (approx. 5 years) |
||
CIO Area |
Input Bits | 1,600 bits (100 words): CIO 0.00 to CIO 99.15 (CIO 00 to CIO 99) | ||
Output Bits | 1,600 bits (100 words): CIO 100.00 to CIO 199.15 (CIO 100 to CIO 199) | |||
Serial PLC Link Words | 1,440 bits (90 words): CIO 200.00 to CIO 289.15 (words CIO 200 to CIO 289) | |||
Work Area (W) | 1,600 bits (100 words): W0.00 to W99.15 (W0 to W99) | |||
Holding Area (H) | 800 bits (50 words): H0.00 to H49.15 (H0 to H49) Bits in this area maintain their ON/OFF status when operating mode is changed. |
|||
Auxiliary Area (A) | Read-only: 7,168 bits (448 words) A0 to A447 Read/write: 4,896 bits (306 words) in words A448 to A753 |
|||
Temporary Relay Area (TR) (TR Area) | 16 bits: TR0 to TR15 | |||
Timer Area (T) | 256 timer numbers (T0 to T255 (separate from counters)) | |||
Counter Area (C) | 256 counter numbers (C0 to C255 (separate from timers)) | |||
Data Memory Area (D) | 2 Kwords: D0 to D2047 Of these, 1,500 words can be saved to the backup memory (built-in EEPROM) using settings in the Auxiliary Area. |
8 Kwords: D0 to D8191 Of these, 7,000 words can be saved to the backup memory (built-in EEP-ROM) using settings in the Auxiliary Area |
||
Operating modes | PROGRAM mode: Program execution is stopped. Preparations can be executed prior to program execution in this mode. MONITOR mode: Programs are executed. Some operations, such as online editing, and changes to present values in I/O memory, are enabled in this mode. RUN mode: Programs are executed. This is the normal operating mode. |