LJ61BT11
Master/local station for MELSEC-L Series.
The CC-Link connects the CPUs of various MELSEC series PLCs within a single network
Feature
- These modules are available as master or local stations for CC-Link
- CC-Link parameters can be set on the Parameter Setting screen of the programming software GX Works 2 for the MELSEC
- When used as local station or standby master station, transmission speed can be set to “automatic flattery”
- High-speed communication is available in remote I/O network mode only when slave stations are remote I/O stations
| Specifications | LJ61BT11 | ||
|---|---|---|---|
| Module type | Master/Slave | ||
| Max. no. of connected stations | 64 | ||
| Max. overall cable distance | m | 1200 (without repeater) | |
| No. of occupied stations | 1–4 stations | ||
| Max. nbr. of link points | per system | 2048 (8192)* | |
| per station | 32 | ||
| Transmission method | Broadcast polling method | ||
| Synchronous method | Frame synchronization | ||
| Encoding method | NRZI method | ||
| Transmission speed | 156 kbps/625 kbps/2.5 Mbps/5 Mbps/10 Mbps | ||
| Transmission path | Bus (RS485) | ||
| I/O points | 32 | ||
| Internal power consumption 5 V DCmA | 460 | ||
| Weight | kg | 0.15 | |
| Dimensions (WxHxD) | mm | 28.5x90x95 | |
| Order information Art. no. | 238099 | ||
The MELSEC Series is constantly looking ahead to meet your future demands and expectations.
High performance and future proof solutions are delivered by the enhanced lineup and network systems. The MELSEC PLC series lineup consists of two main groups:
Modular PLC with the iQ-R and Q Series, Compact PLC with iQ F and FX Series