S8VK-T96024 Bộ nguồn một chiều 960w Omron

11,300,000

Giao hàng COD toàn quốc

Out of stock

Mô Tả Sản Phẩm

S8VK-T96024

Bộ nguồn một chiều 960w Omron

Worldwide 3-phase Power Supply Resistant in tough environments Easy and fast installation The most compact class on the market

Power ratings Input voltage Output Voltage Output current Boost Current Model number
120 W 2-phase and 3-phase
380 to 480 VAC
450 to 600 VDC
24 V 5 A 6 A S8VK-T12024
240 W 24 V 10 A 12 A S8VK-T24024
480 W 24 V 20 A 24 A S8VK-T48024
960 W 3-phase
380 to 480 VAC
24 V 40 A 48 A S8VK-T96024
2-phase
380 to 480 VAC
24 V 32 A

Mounting Brackets

Name Model Qty used
Front-mounting bracket (for 120, 240 and 480 W models) S82Y-VK10F 1
Front-mounting bracket (for 960 W model) S82Y-VK10F 2
Side-mounting bracket (for 120 W model) S82Y-VK10S 1
Side-mounting bracket (for 240 W model) S82Y-VK20S 1
Note: Be sure to use the accessory screws.
Mounting screw tightening torque (recommended): 4.43 to 5.31 lb-in (0.5 to 0.6 Nm)

Ratings, Characteristics, and Functions

Power rating 120 W 240 W
Output voltage 24 V 24 V
Efficiency 3-phase, 400
VAC input *11
89% typ. 89% typ.
Input Voltage range *1 3-phase, 380 to 480 VAC (allowable range: 320 to 576 VAC)
2-phase, 380 to 480 VAC (allowable range: 340 to 576 VAC)
450 to 600 VDC (allowable range: 450 to 810 VDC) *8
Frequency *1 50/60 Hz (47 to 63 Hz)
Current 3-phase, 400
VAC input *11
0.38 A typ. 0.69 A typ.
Power factor
Leakage
current
3-phase, 400
VAC input
3.5 mA max./1.3 mA typ. 3.5 mA max./1.4 mA typ.
Inrush
current (for a
cold start at
25°C) *2
3-phase, 400
VAC input
28 A typ. 29 A typ.
Output Rated output current 5 A 10 A
Boost current 6 A 12 A
Voltage adjustment range *3 22.5 to 29.5 VDC (with V.ADJ) (guaranteed)
Ripple & Noise
voltage *4
3-phase, 400
VAC input *11
160 mV p-p max. at 20 MHz of
bandwidth
190 mV p-p max. at 20 MHz of
bandwidth
Input variation influence *13 0.5% max.
Load variation influence *12 1.5% max.
Temperature
variation
influence
3-phase, 400
VAC input
0.05%/°C max.
Start up time
*2
3-phase, 400
VAC input *11
700 ms typ. 600 ms typ.
Hold time *2 3-phase, 400
VAC input *11
30 ms typ. 20 ms typ.
Additional
functions
Overload protection Yes, automatic reset Yes, automatic reset
Overvoltage protection Yes, 130% or higher of rated output voltage, power shut off (shut off the
input voltage and turn on the input again) *5
Series operation Yes (For up to two Power Supplies, external diodes are required.)
Parallel operation Yes (Refer to Engineering Data) (For up to two Power Supplies)
Output indicator Yes (LED: Green), lighting from 80% to 90% or more of rated voltage
Insulation Withstand voltage 3.0 kVAC for 1 min. (between all input terminals and output terminals)
cutoff current 20 mA
2.5 kVAC for 1 min. (between all input terminals and PE terminal) cutoff
current 20 mA
1.0 kVAC for 1 min. (between all output terminals and PE terminal) cutoff
current 30 mA
Insulation resistance 100 MΩ min. (between all output terminals and all input terminals/PE
terminal) at 500 VDC
Envi-
ronment
Ambient operating temperature -40 to 70°C (However, only startup is guaranteed for between -40°C
to -25°C. (3-phase only)) (Derating is required according to the
temperature.) (with no condensation or icing)
Storage temperature -40 to 85°C (with no condensation or icing)
Ambient operating humidity 0% to 95% (Storage humidity: 0% to 95%)
Vibration resistance 10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z
directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Reliability MTBF 135,000 hrs min.
Life expectancy *10 10 years min.
Con-
struction
Weight 700 g max. 1,000 g max.
Cooling fan No
Degree of protection IP20 by EN/IEC 60529
Standards Harmonic current emissions Conforms to EN 61000-3-2
EMI Conducted
Emission
Conforms to EN 61204-3 Class B EN 55011 Class B
Radiated
Emission
Conforms to EN 61204-3 Class B EN 55011 Class B
EMS Conforms to EN 61204-3 high severity levels
Approved Standards *6 UL Listed: UL 508 *7
EN: EN 50178
Lloyd’s standards *9
ANSI/ISA 12.12.01 *7
UL Listed: UL 508 *7
UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No.60950-1
CSA: CSA C22.2 No.60950-1
EN: EN 50178, EN 60950-1
Lloyd’s standards *9
ANSI/ISA 12.12.01 *7
Conformed Standards SELV (EN 50178),
PELV (EN 60204-1, EN 50178)
Safety of Power Transformers
(EN 61558-2-16)
EN 50274 for Terminal parts
SELV (EN 60950-1/EN 50178/
UL 60950-1)
PELV (EN 60204-1, EN 50178)
Safety of Power Transformers
(EN 61558-2-16)
EN 50274 for Terminal parts
SEMI Conforms to F47-0706 (3-phase, 380 to 480 VAC input)
Power rating 480 W 960 W (768 W *18)
Output voltage 24 V 24 V
Efficiency 3-phase, 400
VAC input *11
91% typ. 92% typ.
Input Voltage range *1 3-phase, 380 to 480 VAC
(allowable range: 320 to 576 VAC)
2-phase, 380 to 480 VAC
(allowable range: 340 to 576 VAC)
450 to 600 VDC (allowable range:
450 to 810 VDC) *8
3-phase, 380 to 480 VAC
(allowable range: 320 to 576 VAC)
2-phase, 380 to 480 VAC
(allowable range: 340 to 576 VAC)
Frequency *1 50/60 Hz (47 to 63 Hz)
Current 3-phase, 400
VAC input *11
1.2 A typ. 2.1 A typ.
Power factor
Leakage
current
3-phase, 400
VAC input
3.5 mA max./1.0 mA typ. 3.5 mA max./1.2 mA typ.
Inrush
current (for a
cold start at
25°C) *2
3-phase, 400
VAC input
28 A typ.
Output Rated output current 20 A 40 A at 3-phase (32 A at 2-phase)
Boost current 24 A 48 A at 3-phase (Not possible at
2-phase)
Voltage adjustment range *3 22.5 to 29.5 VDC (with V.ADJ)
(guaranteed)
22.5 to 29.5 VDC (with V.ADJ)
(guaranteed) *14
Ripple & Noise
voltage *4
3-phase, 400
VAC input *11
130 mV p-p max. at 20 MHz of
bandwidth
90 mV p-p max. at 20 MHz of
bandwidth
Input variation influence *13 0.5% max.
Load variation influence *12 1.5% max.
Temperature
variation
influence
3-phase, 400
VAC input
0.05%/°C max.
Start up time
*2
3-phase, 400
VAC input *11
500 ms typ. 700 ms typ.
Hold time *2 3-phase, 400
VAC input *11
20 ms typ. 20 ms typ.
Additional
functions
Overload protection Yes, automatic reset
Overvoltage protection Yes, 130% or higher of rated output voltage, power shut off (shut off the
input voltage and turn on the input again) *5
Series operation Yes (For up to two Power Supplies, external diodes are required.)
Parallel operation Yes (Refer to Engineering Data) (For up to two Power Supplies)
Output indicator Yes (LED: Green), lighting from 80% to 90% or more of rated voltage
Insulation Withstand voltage 3.0 kVAC for 1 min. (between all input terminals and output terminals)
cutoff current 20 mA
2.5 kVAC for 1 min. (between all input terminals and PE terminal) cutoff
current 20 mA
1.0 kVAC for 1 min. (between all output terminals and PE terminal)
cutoff current 30 mA
Insulation resistance 100 MΩ min. (between all output terminals and all input terminals/PE
terminal) at 500 VDC
Envi-
ronment
Ambient operating temperature -40 to 70°C (However, only startup is guaranteed for between -40°C
to -25°C. (3-phase only)) (Derating is required according to the
temperature.) (with no condensation or icing)
Storage temperature -40 to 85°C (with no condensation or icing)
Ambient operating humidity 0% to 95% (Storage humidity: 0% to 95%)
Vibration resistance 10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z
directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Reliability MTBF 135,000 hrs min.
Life expectancy *10 10 years min.
Con-
struction
Weight 1,600 g max. 2,700 g max.
Cooling fan No
Degree of protection IP20 by EN/IEC 60529
Standards Harmonic current emissions Conforms to EN 61000-3-2 *15
EMI Conducted
Emission
Conforms to EN 61204-3 Class B EN 55011 Class B *16
Radiated
Emission
Conforms to EN 61204-3 Class B EN 55011 Class B *16
EMS Conforms to EN 61204-3 high severity levels
Approved Standards *6 UL Listed: UL 508 *7
UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No.60950-1
CSA: CSA C22.2 No.60950-1
EN: EN 50178, EN 60950-1
Lloyd’s standards
ANSI/ISA 12.12.01 *7
Conformed Standards SELV (EN 60950-1/EN 50178/UL 60950-1)
PELV (EN 60204-1, EN 50178)
Safety of Power Transformers (EN 61558-2-16)
EN 50274 for Terminal parts
SEMI Conforms to F47-0706 (3-phase, 380 to 480 VAC input) *17
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but
the rise in the internal temperature of the Power Supply may result in ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data on Data Sheet for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than 29.5 VDC of the voltage
adjustment range.
When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the
load is not damaged.
*4. A characteristic when the ambient operating temperature is between –25 to 70°C.
*5. Refer to Overvoltage Protection on Data Sheet for the time when input voltage shuts off and input turns on again.
*6. To meet safety standards, the S8VK-T must be protected with an external circuit-breaker or a fuse.
Be sure to use an external circuit-breaker or a fuse. Refer to Precautions for Safe Use on Data Sheet for details.
*7. The following supplementary Fuse/Circuit Breaker must be installed in accordance with NEC.:
Model FAZ-D5/3-NA, FAZ-D5/3-RT or FAZ-D5/3-DU, EATON INDUSTRIES (AUSTRIA) GMBH (E235139),
Model KLKD5, LITTELFUSE INC. (E10480)
*8. Safety Standards for a DC Input
The following standards apply to a 450 to 600 VDC input: UL 60950-1, EN 50178, EN 60950-1, and Lloyd’s standards.
*9. In the case of using side-mounting bracket (S82Y-VK10S, S82YVK20S), Lloyd’s Standards are not applicable.
*10. The value is when rated output current is 50% or less, the ambient operating temperature is 40°C or less, standard
mounting, and rated input voltage.
*11. The value is when both rated output voltage and rated output current are satisfied.
*12. 380 to 480 VAC input, in the range of 0 A to the rated output current.
*13. This is the maximum variation in the output voltage when the input voltage is gradually changed within the allowable
input voltage range at the rated output voltage and rated output current.
*14. Use at 26.4 VDC or lower for 2-phase input.
*15. The S8VK-T Power Supply conforms to EN 61000-3-2 under the following conditions for 2-phase input.
480 W: rated output voltage, and 65% or less of rated output current
960 W: rated output voltage, and 45% or less of rated output current
*16. The S8VK-T Power Supply conforms to EMI under the following conditions for 2-phase input.
480 W: Conforms to class B: rated output voltage, and 65% or less of rated output current/
Conforms to class A: rated output voltage, and 65% to 100% of rated output current
960 W: Conforms to class B: rated output voltage, and 45% or less of rated output current/
Conforms to class A: rated output voltage, and 45% to 100% of rated output current
*17. 480 W: rated output voltage, and 50% or less of rated output current.
960 W: rated output voltage, and 92.5% or less of rated output current.
*18. When using 2-phase input. Refer to 2-Phase Input Operation For 960 W Model in Precautions for Safe Use on Data
Sheet for details.