Input module specifications

Item AC input
RX28 RX10 RX10-TS
Number of input points 8 16 16
Rated input voltage, frequency 100…240 V AC,
50/60 Hz
100…120 V AC,
50/60 Hz
100…120 V AC,
50/60 Hz
Rated input current (mA) 16.4 (200 V AC, 60 Hz)
13.7 (200 V AC, 50 Hz)
8.2 (100 V AC, 60 Hz)
6.8 (100 V AC, 50 Hz)
8.2 (100 V AC, 60 Hz)
6.8 (100 V AC, 50 Hz)
8.2 (100 V AC, 60 Hz)
6.8 (100 V AC, 50 Hz)
Response time (ms) ≤ 20 ≤ 20 ≤ 20
Common terminal arrangement (points/common) 8 16 16
Interrupt function
External interface*3
18-point screw terminal block
Spring-clamp terminal block
Item DC input
RX40C7 RX40C7-TS RX41C4 RX41C4-TS RX42C4 RX70C4 RX71C4 RX72C4
Number of input points 16 16 32 32 64 16 32 64
Rated input voltage (V DC) 24 24 24 24 24 5/12 5/12 5/12
Rated input current (mA, TYP.) 7.0 7.0 4.0 4.0 4.0 1.7
(5 V DC)
4.8
(12 V DC)
1.7
(5 V DC)
4.8
(12 V DC)
1.7
(5 V DC)
4.8
(12 V DC)
Response time (ms) 0.1…70 0.1…70 0.1…70 0.1…70 0.1…70 0.1…70 0.1…70 0.1…70
Common terminal arrangement
(points/common)
16 16 32 32 32 16 32 32
Interrupt function
External interface*3
18-point screw terminal block
40-pin connector ● (2x) ● (2x)
Spring-clamp terminal block
Item DC high-speed input DC input (with diagnostic functions)
RX40PC6H RX40NC6H RX41C6HS RX61C6HS RX40NC6B
Number of input points 16 16 32 32 16
Rated input voltage (V DC) 24 24 24 5 24
Rated input current (mA) 6.0 6.0 6.0 6.0 6.0
Response time 5 µs…70 ms 5 µs…70 ms 1 µs…70 ms 1 µs…70 ms 1 µs…70 ms
Common terminal arrangement
(points/common)
8
(positive common)
8
(negative common)
32
(positive/negative common)
32
(positive/negative common)
16
(negative common)
Interrupt function
SIL 2-compliant *4
Diagnostic function*5
Disconnection detection
External interface*3
18-point screw terminal block
40-pin connector
*3: For applicable options, please refer to the relevant product manual.
*4: When used together with a SIL 2 redundant control system (SIL 2 is supported in the module firmware version of “02” or later).
*5: For more information about diagnostic functions, please refer to the relevant product manual.