K8AK-VW3 Rơ le bảo vệ điện áp Omron

Ideal for Voltage Monitoring for Industrial Facilities and Equipment. Monitor for overcurrents and undercurrents simultaneously.

• Monitor for overvoltages and undervoltages simultaneously. Separate settings and outputs supported for overvoltages and undervoltages.

• Manual resetting and automatically resetting supported by one Relay.

• Pre-alarm Monitoring Mode.

• Two SPDT output relays, 5 A at 250 VAC (resistive load).

• Process control signal (0 to 10 V) and current splitter input supported.

• Output status can be monitored using LED indicator.

• Input frequency of 40 to 500 Hz supported.

• Inputs are isolated from the power supply.

Setting rangePower supply voltageModel
1 to 10 V AC/DC
3 to 30 V AC/DC
15 to 150 V AC/DC
24 VAC/DCK8AK-VW2 24 VAC/DC
100 to 240 VACK8AK-VW2 100-240 VAC
20 to 200 V AC/DC
30 to 300 V AC/DC
60 to 600 V AC/DC
24 VAC/DCK8AK-VW3 24 VAC/DC
100 to 240 VACK8AK-VW3 100-240 VAC

Input Range

ModelRange*Connection terminalSetting rangeInput impedanceOverload capacity
K8AK-VW20 to 10 V
AC/DC
V1-COM1 to 10 V
AC/DC
3 to 30 V
AC/DC
15 to 150 V
AC/DC
Approx. 120 kΩContinuous input at
115% of maximum input.
10 s at 125%
(up to 600 VAC)
0 to 30 V
AC/DC
V2-COMApprox. 320 kΩ
0 to 150 V
AC/DC
V3-COMApprox. 1.6 MΩ
K8AK-VW30 to 200 V
AC/DC
V1-COM20 to 200 V
AC/DC
30 to 300 V
AC/DC
60 to 600 V
AC/DC
Approx. 1.2 MΩ
0 to 300 V
AC/DC
V2-COMApprox. 1.7 MΩ
0 to 600 V
AC/DC
V3-COMApprox. 3.1 MΩ

* The range is selected using connected terminals.

Ratings

Power supply
voltage
Isolated power supply24 VAC/DC
100 to 240 VAC
Power consumption24 VAC/DC: 2.0 VA/1.1 W max.
100 to 240 VAC: 4.6 VA max.
Operating value setting range
(AL1 and AL2)
10% to 100% of the maximum value of the setting range
K8AK-VW2:
1 to 10 V AC/DC
3 to 30 V AC/DC
15 to 150 V AC/DC
K8AK-VW3:
20 to 200 V AC/DC
30 to 300 V AC/DC
60 to 600 V AC/DC
Operating value100% operation at set value
Reset value5% of operating value (fixed)
Reset methodManual reset/automatic reset (switchable)
Note: Manual reset: Turn OFF power supply for 1 s or longer.
Operating time setting range (T)0.1 to 30 s
Power ON lock time (LOCK)1 s or 5 s (Switched using DIP switch.)
IndicatorsPower (PWR): Green, Relay output (RY): Yellow, Alarm outputs (AL1, AL2): Red
Input impedanceRefer to Input Range on previous page.
Output relaysTwo SPDT relays (NC operation)
Output relay ratingsRated load
Resistive load
5 A at 250 VAC
5 A at 30 VDC
Maximum switching capacity: 1,250 VA, 150 W
Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life:
5 A at 250 VAC or 30 VDC: 50,000 operations
3 A at 250 VAC or 30 VDC: 100,000 operations
Ambient operating temperature-20 to 60°C (with no condensation or icing)
Storage temperature-25 to 65°C (with no condensation or icing)
Ambient operating humidity25% to 85% (with no condensation)
Storage humidity25% to 85% (with no condensation)
Altitude2,000 m max.
Terminal screw tightening torque0.49 to 0.59 N·m
Terminal wiring methodRecommended wire
Solid wire: 2.5 mm2
Twisted wires: AWG16, AWG18
Note: 1. Ferrules with insulating sleeves must be used with twisted wires.
Note: 2. Two wires can be twisted together.
Recommended ferrules
Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact
Al 1-8RD (for AWG18) manufactured by Phoenix Contact
Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact
Case colorN1.5
Case materialPC and ABS, UL 94 V-0
WeightApprox. 150 g
MountingMounts to DIN Track.
Dimensions22.5 × 90 × 100 mm (W×H×D)

Specifications

Allowable operating voltage range85% to 110% of rated power supply voltage
Allowable operating frequency range50/60 Hz ±5 Hz
Input frequency range40 to 500 Hz
Overload capacityContinuous input at 115% of maximum input, 10 s at 125% (up to 600 VAC).
Repeat
error
Operating value±0.5% full scale (at 25°C and an ambient humidity of 65% at the rated power
supply voltage, DC and 50/60 Hz sine wave input)
Operating time±50 ms (at 25°C and 65% humidity, rated power supply voltage)
Applicable
standards
Conforming
standards
EN 60947-5-1
Installation environment (pollution level 2, installation category III)
EMCEN 60947-5-1
Safety standardsUL 508 (Recognition), Korean Radio Waves Act (Act 10564),
CSA: C22.2 No.14, CCC: GB/T 14048.5
Insulation resistance20 MΩ min.
Between all external terminals and the case
Between all power supply terminals and all input terminals
Between all power supply terminals and all output terminals
Between all input terminals and all output terminals
Dielectric strength2,000 VAC for 1 min
Between all external terminals and the case
Between all power supply terminals and all input terminals
Between all power supply terminals and all output terminals
Between all input terminals and all output terminals
Noise immunity1,500 V power supply terminal common/normal mode
Square-wave noise of ±1 μs/100 ns pulse width with 1-ns rise time
Vibration resistanceFrequency: 10 to 55 Hz, 0.35-mm single amplitude
10 sweeps of 5 min each in X,Y, and Z directions
Shock resistance100 m/s2, 3 times each in 6 directions along 3 axes
Degree of protectionTerminals: IP20