UL508, CSA22.2 No.14, and EN60947-4-3
Rơ le bán dẫn tích hợp tản nhiệt G3PE-535B-3N Omron
252 lượt xem
Ngày: 01/06/2019
Hết Hàng
Thông tin sản phẩm
5,172,000₫
Hết hàng
0816914999 (Liên hệ mua hàng) Email: sales@minhquangelectric.com THỜI GIAN LÀM VIỆC: Thứ 2 - thứ 6 / 8:00 AM - 5:00 PM Thứ 7 / 9:00 AM - 11:00 AM (Email only)
0969.100.802 (Dịch vụ kỹ thuật) Email: services@minhquangelectric.com THỜI GIAN LÀM VIỆC: Thứ 2 - thứ 6 / 8:00 AM - 5:00 PM Thứ 7 / 9:00 AM - 11:00 AM (Email only)
THÔNG TIN SẢN PHẨM
G3PE-535B-3N
Rơ le bán dẫn tích hợp tản nhiệt Omron
Compact, Slim-profile SSRs with Heat Sinks. Models with No Zero Cross for a Wide Range of Applications
• RoHS compliant.
• Models also available with no zero cross
• Surge pass protection improved surge dielectric strength for output currents. (OMRON testing)
• Compact with a slim profile.
• Mount to DIN Track or with screws.
• Conforms to UL, CSA, and EN standards (TÜV certification).
Certification
Ratings
Input (at an Ambient Temperature of 25°C)
Model | Rated voltage | Operating voltage range | Rated input current | Voltage level | |
---|---|---|---|---|---|
Must operate voltage | Must release voltage | ||||
G3PE-[][][]B | 12 to 24 VDC | 9.6 to 30 VDC | 7 mA max. | 9.6 VDC max. | 1.0 VDC max. |
G3PE-[][][]BL | 15 mA max. |
Output
Model | G3PE- 215B(L) | G3PE- 225B(L) | G3PE- 235B(L) | G3PE- 245B(L) | G3PE- 515B(L) | G3PE- 525B(L) | G3PE- 535B(L) | G3PE- 545B(L) |
---|---|---|---|---|---|---|---|---|
Rated load voltage | 100 to 240 VAC (50/60 Hz) | 200 to 480 VAC (50/60 Hz) | ||||||
Load voltage range | 75 to 264 VAC (50/60 Hz) | 180 to 528 VAC (50/60 Hz) | ||||||
Applicable load current * | 0.1 to 15 A (at 40 °C) | 0.1 to 25 A (at 40 °C) | 0.5 to 35 A (at 25 °C) | 0.5 to 45 A (at 25 °C) | 0.1 to 15 A (at 40 °C) | 0.1 to 25 A (at 40 °C) | 0.5 to 35 A (at 25 °C) | 0.5 to 45 A (at 25 °C) |
Inrush current resistance | 150 A (60 Hz, 1 cycle) | 220 A (60 Hz, 1 cycle) | 440 A (60 Hz, 1 cycle) | 150 A (60 Hz, 1 cycle) | 220 A (60 Hz, 1 cycle) | 440 A (60 Hz, 1 cycle) | ||
Permissible I2t (reference value) | 121A2s | 260A2s | 1,260A2s | 128A2s | 1,350A2s | 6,600A2s | ||
Applicable load (resistive load) | 3 kW (at 200 VAC) | 5 kW (at 200 VAC) | 7 kW (at 200 VAC) | 9 kW (at 200 VAC) | 6 kW (at 400 VAC) | 10 kW (at 400 VAC) | 14 kW (at 400 VAC) | 18 kW (at 400 VAC) |
Temperature in Engineering Data on Data Sheet.
Characteristics
Model | G3PE -215B | G3PE -225B | G3PE -235B | G3PE -245B | G3PE -215BL | G3PE -225BL | G3PE -235BL | G3PE -245BL |
---|---|---|---|---|---|---|---|---|
Operate time | 1/2 of load power source cycle + 1 ms max. | 1 ms max. | ||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop | 1.6 V (RMS) max. | |||||||
Leakage current | 10 mA max. (at 200 VAC) | |||||||
Insulation resistance | 100 MΩ min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance | 10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track) | |||||||
Shock resistance | Destruction: 294 m/s2 (Mounted to DIN track) | |||||||
Ambient storage temperature | – 30 to 100 °C (with no icing or condensation) | |||||||
Ambient operating temperature | – 30 to 80 °C (with no icing or condensation) | |||||||
Ambient operating humidity | 45% to 85% | |||||||
Weight | Approx. 240 g | Approx. 400 g | Approx. 240 g | Approx. 400 g |
Model | G3PE -515B | G3PE -525B | G3PE -535B | G3PE -545B | G3PE -515BL | G3PE -525BL | G3PE -535BL | G3PE -545BL |
---|---|---|---|---|---|---|---|---|
Operate time | 1/2 of load power source cycle + 1 ms max. | 1 ms max. | ||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop | 1.8 V (RMS) max. | |||||||
Leakage current | 20 mA max. (at 480 VAC) | |||||||
Insulation resistance | 100 MΩ min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance | 10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track) | |||||||
Shock resistance | Destruction: 294 m/s2 (Mounted to DIN track) | |||||||
Ambient storage temperature | – 30 to 100 °C (with no icing or condensation) | |||||||
Ambient operating temperature | – 30 to 80 °C (with no icing or condensation) | |||||||
Ambient operating humidity | 45% to 85% | |||||||
Weight | Approx. 240 g | Approx. 400 g | Approx. 240 g | Approx. 400 g |