• Downsizing achieved through optimum design of heat sink.
• Mounting possible via screws or via DIN track.
• Close mounting possible for linking terminals. (Except for G3PA-260B-VD and G3PA-450B-VD-2.)
• Applicable with 3-phase loads.
• Replaceable power element cartridges.
• Comply with VDE 0160 (finger protection), with a dielectric strength of 4,000 V between input and load.
• Certified by UL, CSA, and VDE (reinforced insulation). *
* Only UL and CSA certification applies to model numbers that end in -VD-X.
Ratings (at an Ambient Temperature of 25°C)
Input
Model | Rated voltage | Operating Voltage range | Input current impedance | Voltage level | |
---|---|---|---|---|---|
Must operate voltage | Must release voltage | ||||
G3PA-210B-VD-X | 5 to 24 VDC | 4 to 30 VDC | 7 mA max. | 4 VDC max. | 1 VDC min. |
G3PA-220B-VD-X | |||||
G3PA-240B-VD | |||||
G3PA-260B-VD | |||||
G3PA-210BL-VD | 5 to 24 VDC | 4 to 30 VDC | 20 mA max. | 4 VDC max. | 1 VDC min. |
G3PA-220BL-VD | |||||
G3PA-240BL-VD | |||||
G3PA-260BL-VD | |||||
G3PA-210B-VD | 24 VAC | 19.2 to 26.4 VAC | 1.4 kΩ±20% | 19.2 VAC max. | 4.8 VAC min. |
G3PA-220B-VD | |||||
G3PA-240B-VD | |||||
G3PA-260B-VD | |||||
G3PA-420B-VD | 12 to 24 VDC | 9.6 to 30 VDC | 7 mA max. | 9.2 VDC max. | 1 VDC min. |
G3PA-430B-VD | |||||
G3PA-420B-VD-2 | |||||
G3PA-430B-VD-2 | |||||
G3PA-450B-VD-2 |
Output
Model | Rated load voltage | Load voltage range | Load current | Inrush current | VDRM (reference value) |
---|---|---|---|---|---|
G3PA-210B(L)-VD(-X) | 24 to 240 VAC (50/60 Hz) | 19 to 264 VAC (50/60 Hz) | 0.1 to 10 A at 40°C | 150 A (60 Hz, 1 cycle) | 600 V (VDRM) |
G3PA-220B(L)-VD(-X) | 0.1 to 20 A at 40°C | 220 A (60 Hz, 1 cycle) | |||
G3PA-240B(L)-VD | 0.5 to 40 A at 40°C | 440 A (60 Hz, 1 cycle) | |||
G3PA-260B(L)-VD | 0.5 to 60 A at 40°C | 440 A (60 Hz, 1 cycle) | |||
G3PA-420B-VD | 200 to 400 VAC (50/60 Hz) | 180 to 440 VAC (50/60 Hz) | 0.5 to 20 A at 30°C | 220 A (60 Hz, 1 cycle) | 1,000 V (VDRM) |
G3PA-430B-VD | 0.5 to 30 A at 30°C | 440 A (60 Hz, 1 cycle) | |||
G3PA-420B-VD-2 | 200 to 480 VAC (50/60 Hz) | 180 to 528 VAC (50/60 Hz) | 0.5 to 20 A at 30°C | 220 A (60 Hz, 1 cycle) | 1,200 V (VDRM) |
G3PA-430B-VD-2 | 0.5 to 30 A at 30°C | 440 A (60 Hz, 1 cycle) | |||
G3PA-450B-VD-2 | 0.5 to 50 A at 30°C | 440 A (60 Hz, 1 cycle) |
Refer to Engineering Data for further details.
Characteristics
Item | G3PA- 210B(L) -VD(-X) | G3PA- 220B(L) -VD(-X) | G3PA- 240B(L) -VD | G3PA- 260B(L) -VD | G3PA- 420B -VD | G3PA- 420B -VD-2 | G3PA- 430B -VD | G3PA- 430B -VD-2 | G3PA- 450B -VD-2 |
---|---|---|---|---|---|---|---|---|---|
Operate time | 1/2 of load power source cycle + 1 ms max. (DC Input, -B models) 1 1/2 of load power source cycle + 1 ms max. (AC Input) 1 ms max. (-BL models) | ||||||||
Release time | 1/2 of load power source cycle + 1 ms max. (DC Input) 1 1/2 of load power source cycle + 1 ms max. (AC Input) | ||||||||
Output ON voltage drop | 1.6 V (RMS) max. | 1.8 V (RMS) max. | |||||||
Leakage current | 5 mA max. (at 100 VAC) 10 mA max. (at 200 VAC) | 10 mA max. (at 100 VAC) 20 mA max. (at 200 VAC) | 20 mA max. (at 400 VAC) | 20 mA max. (at 480 VAC) | 20 mA max. (at 400 VAC) | 20 mA max. (at 480 VAC) | |||
I2t | 260 A2s | 1,260 A2s | 260 A2s | 1,800 A2s | 1,800 A2s | 1,800 A2s | |||
Insulation resistance | 100 MΩ min. (at 500 VDC) | ||||||||
Dielectric strength | 4,000 VAC, 50/60 Hz for 1 min | ||||||||
Vibration resistance | Destruction: 10 to 55 to 10 Hz, 0.375-mm single amplitude (Mounted to DIN track) | ||||||||
Shock resistance | Destruction: 300 m/s2 (mounted to DIN track) | ||||||||
Ambient temperature | Operating: -30°C to 80°C (with no icing or condensation) Storage: -30°C to 100°C (with no icing or condensation) | ||||||||
Certified standards | UL508, CSA C22.2 (No.14, No.950), EN60950-1 File No. 5915ÜG | UL508, CSA C22.2 (No.14), EN60947-4-3 File No. 6642ÜG | UL508, CSA C22.2 (No.14), EN60947-4-3 File No. 133127ÜG | UL508, CSA C22.2 (No.14), EN60947-4-3 File No. 6642ÜG | UL508, CSA C22.2 (No.14), EN60947-4-3 File No. 133127ÜG | ||||
EMC | Emission: EN55011 Group 1 Class A Immunity: EN61000-6-2 | ||||||||
Ambient humidity | Operating: 45% to 85% | ||||||||
Weight | Approx. 260 g | Approx. 340 g | Approx. 460 g | Approx. 900 g | Approx. 290 g | Approx. 290 g | Approx. 410 g | Approx. 410 g | Approx. 900 g |