Rơ le dẹt G2R-2-SND DC24 Omron

399 lượt xem

Ngày: 01/06/2019

Tình trạng : Còn Hàng

Thông tin sản phẩm

175,000

Xin vui lòng liên hệ theo thông tin dưới dây

0816914999 (Liên hệ mua hàng) Email: sales@minhquangelectric.com THỜI GIAN LÀM VIỆC: Thứ 2 - thứ 6 / 8:00 AM - 5:00 PM Thứ 7 / 9:00 AM - 11:00 AM (Email only)

0969.100.802 (Dịch vụ kỹ thuật) Email: services@minhquangelectric.com THỜI GIAN LÀM VIỆC: Thứ 2 - thứ 6 / 8:00 AM - 5:00 PM Thứ 7 / 9:00 AM - 11:00 AM (Email only)

Rơ le dẹt G2R-2-SND DC24 Omron

Slim and Space-saving Power Plug-in Relay

• Reduces wiring work by 60% when combined with the P2RF-[]-PU Push-In Plus Socket

(according to actual OMRON measurements).

• Lockable test button models available.

• Built-in mechanical operation indicator.

• Provided with nameplate.

• AC type is equipped with a coil-disconnection self-diagnostic function (LED type).

• High switching power (1-pole: 10 A).

Coil Ratings

Rated voltageRated current*Coil
resistance
Coil inductance (H)
(ref. value)
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consumption
(approx.)
50 Hz60 HzArmature
OFF
Armature
ON
% of rated voltage
AC24 V43.5 mA37.4 mA253 Ω0.811.5580% max.30% max.110%0.9 VA at 60 Hz
110 V9.5 mA8.2 mA5,566 Ω13.3326.83
120 V8.6 mA7.5 mA7,286 Ω16.1332.46
230 V4.4 mA3.8 mA27,172 Ω72.68143.9
240 V4.2 mA3.7 mA27,800 Ω90.58182.34
Rated voltageRated current*Coil
resistance
Coil inductance (H)
(ref. value)
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consumption
(approx.)
Armature
OFF
Armature
ON
% of rated voltage
DC6 V87.0 mA69 Ω0.250.4870% max.15% min.110%0.53 W
12 V43.2 mA278 Ω0.982.35
24 V21.6 mA1,113 Ω3.68.25
48 V11.4 mA4,220 Ω15.229.82

Note:
1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of
+15%/-20% for the AC rated current and ±10% for the DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage is the maximum possible value of the voltage that can be applied to the relay coil.
It is not the maximum voltage that can be applied continuously.

Contact Ratings

Number of poles1 pole2 poles
LoadResistive load
(cosΦ = 1)
Inductive load
(cosΦ = 0.4; L/R = 7 ms)
Resistive load
(cosΦ = 1)
Inductive load
(cosΦ = 0.4; L/R = 7 ms)
Rated load10 A at 250 VAC;
10 A at 30 VDC
7.5 A at 250 VAC;
5 A at 30 VDC
5 A at 250 VAC;
5 A at 30 VDC
2 A at 250 VAC;
3 A at 30 VDC
Rated carry current10 A5 A
Max. switching voltage440 VAC, 125 VDC380 VAC, 125 VDC
Max. switching current10 A5 A
Max. switching power2,500 VA, 300 W1,875 VA, 150 W1,250 VA, 150 W500 VA, 90 W
Failure rate (reference value) *100 mA at 5 VDC10 mA at 5 VDC

Note: P level: λ60 = 0.1 x 10-6/operation
*This value was measured at a switching frequency of 120 operations per minute.

Characteristics

Item1 pole2 poles
Contact configrationSPDT
Contact structureSingle
Contact resistance100 mΩ max.
Operate (set) time15 ms max.
Release (reset) timeAC: 10 ms max.; DC: 5 ms max.
(w/built-in diode: 20 ms max.)
AC: 15 ms max.; DC: 10 ms max.
(w/built-in diode: 20 ms max.)
Max. operating
frequency
Mechanical: 18,000 operations/hr
Electrical: 1,800 operations/hr (under rated load)
Insulation resistance1,000 MΩ min. (at 500 VDC)
Dielectric strength *5,000 VAC, 50/60 Hz for 1 min between coil and
contacts;
1,000 VAC, 50/60 Hz for 1 min between contacts
of same polarity
5,000 VAC, 50/60 Hz for 1 min between coil and
contacts;
3,000 VAC, 50/60 Hz for 1 min between contacts
of different polarity
1,000 VAC, 50/60 Hz for 1 min between contacts
of same polarity
Vibration resistanceDestruction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Shock resistanceDestruction: 1,000 m/s2
Malfunction: 200 m/s2 when energized; 100 m/s2 when not energized
EnduranceMechanical:
AC coil: 10,000,000 operations min.;
DC coil: 20,000,000 operations min. (at 18,000 operations/hr)
Electrical: 100,000 operations min. (at 1,800 operations/hr under rated load) (DC coil type)
Ambient temperatureOperating: -40°C to 70°C (with no icing or condensation)
Ambient humidityOperating: 5% to 85%
WeightApprox. 20 g

Note: Values in the above table are the initial values.
*These values are relay only. Prease refer to the “Products Related to Common Sockets and DIN Tracks Data Sheet” for connecting sockets.

Approved Standards

UL 508 (File No. E41643)

ModelContact formCoil ratingsContact ratingsOperations
G2R-1-S (S)SPDT5 to 110 VDC
6 to 240 VAC
10 A, 30 VDC (resistive)
10 A, 250 VAC (general use)
100 × 103
TV-3 (NO contact only)25 × 103
G2R-2-S (S)DPDT5 A, 30 VDC (resistive)
5 A, 250 VAC (general use)
100 × 103
TV-3 (NO contact only)25 × 103

IEC/VDE (Certificate No. 40015012 EN 61810-1)

Contact formCoil ratingsContact ratingsOperations
1 pole6, 12, 24, 48 VDC
24, 110, 120, 230,
240 VAC
5 A, 440 VAC (cosφ = 1.0)
10 A, 250 VAC (cosφ = 1.0)
10 A, 30 VDC (0 ms)
100 × 103
2 poles6, 12, 24, 48 VDC
24, 110, 120, 230,
240 VAC
5 A, 250 VAC (cosφ =1.0)
5 A, 30 VDC (0 ms)
100 × 103

CSA 22.2 No.0, No.14 (File No. LR31928)

ModelContact formCoil ratingsContact ratingsOperations
G2R-1-S (S)SPDT5 to 110 VDC
6 to 240 VAC
10 A, 30 VDC (resistive)
10 A, 250 VAC (general use)
100 × 103
TV-3 (NO contact only)25 × 103
G2R-2-S (S)DPDT5 A, 30 VDC (resistive)
5 A, 250 VAC (general use)
100 × 103
TV-3 (NO contact only)25 × 103

LR

Number of polesCoil ratingsContact ratingsOperations
1 pole5 to 110 VDC
6 to 240 VDC
10 A, 250 VAC (general use)
7.5 A, 250 VAC (PF0.4)
10 A, 30 VDC (resistive)
5A, 30VDC (L/R=7ms)
100 × 103
2 poles5 to 110 VDC
6 to 240 VDC
5 A, 250 VAC (general use)
2 A, 250 VAC (PF0.4)
5 A, 30 VDC (resistive)
3A, 30VDC (L/R=7ms)
100 × 103
NHẬN XÉT SẢN PHẨM